VSR16

 VSR16 DB

Voltage taps for round conductors

Nr. CE-VSRL16/ CE-VSRN16

 

  • One-handed and safe tapping of voltage
  • No tools required
  • Safe mounting

 

 

 

 

Contact

Voltage taps for round conductors

The VSR tapping clamp allows fast and reliable measurement on existing systems. For this purpose, the VSR tapping clamp branches off a fused measuring voltage from an insulated wire with only one turn of the hand. The fuse is located directly on the primary conductor, guaranteeing optimum safety. Since a secure voltage for measurement is rarely available in existing sites, the VSR tapping clamp is an ideal addition for your plants.

  • icon Technical specifications
  • icon Downloads
  • icon Ordering information
Maximum voltage 400 V
Test voltage casing - ground 3kV / 50Hz
Pulse casing - ground 6KV 1,2/ 50μs
Maximum current 2 A
Voltage drop < 500m VAC
Type of protection 5 x 25 mm, 2 A (with indicator)
Max 2A SIBA DIN41576-2
Short circuit current 6kA @ 400V/50 Hz
Protection class IP20
Ambient temperature –5…+40°C
Suitable for PVC and XLPE, stranded and solid conductors
Torque 1.5 Nm multiple use
2.0 Nm single use

 

 

CE-VSRL16

Fused phase terminal black, for cable mounting (cable diameter  6-16 mm²)

CE-VSRN16

Unfused neutral terminal blue, for cable mounting (cable diameter 6-16 mm²)

We use cookies on our website. Some of them are essential for the operation of the site, while others help us to improve this site and the user experience (tracking cookies). You can decide for yourself whether you want to allow cookies or not. Please note that if you reject them, you may not be able to use all the functionalities of the site.