VSR16

 VSR16 DB

Voltage taps for round conductors

Nr. CE-VSRL16/ CE-VSRN16

 

  • One-handed and safe tapping of voltage
  • No tools required
  • Safe mounting

 

 

 

 

Contact

Voltage taps for round conductors

The VSR tapping clamp allows fast and reliable measurement on existing systems. For this purpose, the VSR tapping clamp branches off a fused measuring voltage from an insulated wire with only one turn of the hand. The fuse is located directly on the primary conductor, guaranteeing optimum safety. Since a secure voltage for measurement is rarely available in existing sites, the VSR tapping clamp is an ideal addition for your plants.

  • icon Technical specifications
  • icon Downloads
  • icon Ordering information
Maximum voltage 400 V
Test voltage casing - ground 3kV / 50Hz
Pulse casing - ground 6KV 1,2/ 50μs
Maximum current 2 A
Voltage drop < 500m VAC
Type of protection 5 x 25 mm, 2 A (with indicator)
Max 2A SIBA DIN41576-2
Short circuit current 6kA @ 400V/50 Hz
Protection class IP20
Ambient temperature –5…+40°C
Suitable for PVC and XLPE, stranded and solid conductors
Torque 1.5 Nm multiple use
2.0 Nm single use

 

 

CE-VSRL16

Fused phase terminal black, for cable mounting (cable diameter  6-16 mm²)

CE-VSRN16

Unfused neutral terminal blue, for cable mounting (cable diameter 6-16 mm²)